VENTINOX RIGIDFACTORY-BUILT LINING SYSTEM INSTALLATION AND OPERATING INSTRUCTIONSPrinted in Canada
Figure 2TherMix Field Benets TherMix Ceramic BlanketsZero-clearance to combustibles Yes YesEase-of-installation Yes YesDiculties with Osets No YesS
TABLE 2: CROSS SECTION AREA OF LINERLiner Size CS Area Oval Liner Size Oval Dimensions CS AreaRound 5" 19.62in2Round 6" 28.46in2 Oval 6"
Attaching a ceramic blanket1/2" of ProFoilVENTINOX LINING SYSTEM -12Roll out the insulation blanket on a clean surface, foil face down. Lay the l
Installation and Operating InstructionsRead these instructions and keep them for future reference.Before installing this liner, consult your local bui
For a new masonry chimney liner installation make sure that the masonry chimney construction and clearances between the chimney exterior and combustib
GENERAL INFORMATIONCREOSOTEWhen wood is burned slowly, it produces tar and other organic vapours, which combine with expelled moisture to form creosot
INSTALLATION GUIDELINESDuraVent Liners venting gas or oil appliances do not require a minimum clearance or insulation between the outside of the liner
8. Installation of wall radiation shield through a combustible wall.• From inside, frame a hole14 1/2" x 14 1/2" (368 mm x 368 mm) in the
Fig. 8 - Lining sustem for new replace installationFig. 9 - Existing replace relining installationFig. 107. Twist lock the rain cap to the top of t
General Guidelines: Duravent Liners have been tested and are listed to UL 1777 and ULC-S635 standard at zero clearance to combustibles and for use wit
ProFoil ceramic blanketVENTINOX LINING SYSTEM - 9METHOD #1:THERMIX BENEFITS AT-A-GLANCE:• No Health Risks: Non-brous, non-toxic, inert and manufactu